Copper Conductor, XLPE Insulated, Copper Tape Screen, Double Galvanized Steel Tape, PVC Sheathed – 2 Core

For power plants and switchgears as well as for installation of substations if ground conditions are propone to mechanical demage. Also used in urban network, household feeders.

SNI IEC 60502-1; SNI 0255

Category:

Description

Cross-sectional area (mm²) Nominal Thickness Insulation (mm) Nominal Thickness Sheath (mm) Overall Diameter (approx., mm) Cable Weight (approx., kg/km) Bending Radius (mm) Max. DC Conductor Resistance at 20°C (Ω/km) Max. AC Conductor Resistance at 90°C (Ω/km) Capacitance (approx., μF/km)
1.5 0.7 1.8 6.0 110 60 12.1 15.0 0.21
2.5 0.7 1.8 6.8 160 68 7.41 9.2 0.20
4 0.7 1.8 7.6 220 76 4.61 5.7 0.19
6 0.7 1.8 8.6 300 86 3.08 3.8 0.18
10 0.7 1.8 10.0 430 100 1.83 2.3 0.17
2 CORE DIMENSIONAL AND ELECTRICAL DATA (Part 1)
Cross-sectional area (mm²) Reactance (approx., Ω/km) Impedance at 90°C (approx., Ω/km) Inductance (approx., mH/km) Voltage Drop at 90°C (approx., mV/A/m) Max. Current Carrying Capacity at 30°C (A) in Air Max. Current Carrying Capacity at 30°C (A) In Ground Max. Short circuit current at 1 sec. (kA)
1.5 0.08 12.0 0.4 44 20 24 1.2
2.5 0.07 7.5 0.35 26 27 34 1.8
4 0.06 4.9 0.3 17 36 47 2.5
6 0.05 3.2 0.25 12 47 61 3.5
10 0.04 1.9 0.2 7 65 85 5.5
2 CORE DIMENSIONAL AND ELECTRICAL DATA (Part 2)